Magnetic-inductive flow meter SM6000

Giá: Liên hệ

Số lượng
- +

Magnetic-inductive flow meter SM6000

SMR12GGXFRKG/US-100

Application
ApplicationTotalizer function; for industrial applications
Installationconnection to pipe by means of an adapter
MediaConductive liquids; water; water-based media
Note on media
conductivity: ≥ 20 µS/cm
viscosity: < 70 mm²/s (40 °C)
Medium temperature [°C]-10...70
Pressure rating [bar]16
MAWP (for applications according to CRN) [bar]17.7
Electrical data
Operating voltage [V]18...30 DC; (according to EN 50178 SELV/PELV)
Current consumption [mA]95; (24 V)
Min. insulation resistance [MΩ]100; (500 V DC)
Protection classIII
Reverse polarity protectionyes
Power-on delay time [s]5
Inputs / outputs
Number of inputs and outputsNumber of digital outputs: 2; Number of analog outputs: 1
Inputs
Inputscounter reset
Outputs
Total number of outputs2
Output signalswitching signal; analog signal; pulse signal; IO-Link; (configurable)
Electrical designPNP/NPN
Number of digital outputs2
Output functionnormally open / closed; (configurable)
Max. voltage drop switching output DC [V]2
Permanent current rating of switching output DC [mA]200
Number of analog outputs1
Analog current output [mA]4...20; (scalable)
Max. load [Ω]500
Analog voltage output [V]0...10; (scalable)
Min. load resistance [Ω]2000
Pulse outputflow rate meter
Short-circuit protectionyes
Type of short-circuit protectionyes (non-latching)
Overload protectionyes
Measuring/setting range
Measuring range
0.1...25 l/min0.005...1.5 m³/h
Display range
-30...30 l/min-1.8...1.8 m³/h
Resolution
0.02 l/min0.002 m³/h
Set point SP
0.25...25 l/min0.015...1.5 m³/h
Reset point rP
0.1...24.9 l/min0.005...1.495 m³/h
Analog start point ASP
0...20 l/min0...1.2 m³/h
Analog end point AEP
5...25 l/min0.3...1.5 m³/h
In steps of
0.02 l/min0.002 m³/h
Volumetric flow quantity monitoring
Pulse value0.00001...30 000 m³
Pulse length [s]0,01...2
Temperature monitoring
Measuring range [°C]-20...80
Resolution [°C]0.2
Set point SP [°C]-19.2...80
Reset point rP [°C]-19.6...79.6
Analog start point [°C]-20...60
Analog end point [°C]0...80
In steps of [°C]0.2
Accuracy / deviations
Flow monitoring
Accuracy (in the measuring range)± (0,8 % MW + 0,5 % MEW)
Repeatability± 0,2% MEW
Temperature monitoring
Accuracy [K]± 2,5 (Q > 1 l/min)
Reaction times
Flow monitoring
Response time [s]0.15; (dAP = 0)
Delay time programmable dS, dr [s]0...50
Damping for the switching output dAP [s]0...5
Temperature monitoring
Dynamic response T05 / T09 [s]T09 = 20 (Q > 1 l/min)
Software / programming
Parameter setting optionsFlow monitoring; quantity meter; Preset counter; Temperature monitoring; hysteresis / window; normally open / closed; switching logic; current/voltage/pulse output; Start-up delay; display can be deactivated; Display unit
Interfaces
Communication interfaceIO-Link
Transmission typeCOM2 (38,4 kBaud)
IO-Link revision1.1
SDCI standardIEC 61131-9
IO-Link device ID569 / 00 02 39 h
ProfilesSmart Sensor: Process Data Variable; Device Identification, Device Diagnosis
SIO modeyes
Required master port classA
Process data analogue3
Process data binary2
Min. process cycle time [ms]5
Operating conditions
Ambient temperature [°C]-10...60
Storage temperature [°C]-25...80
ProtectionIP 67
Tests / approvals
EMC
DIN EN 60947-5-9
Shock resistance
DIN IEC 68-2-2720 g (11 ms)
Vibration resistance
DIN IEC 68-2-65 g (10...2000 Hz)
MTTF [years]162
Pressure equipment directivesound engineering practice; can be used for group 2 fluids; group 1 fluids on request
Mechanical data
Weight [g]542.5
Materialstainless steel (1.4404 / 316L); PBT-GF20; PC; FKM; TPE
Materials (wetted parts)stainless steel (1.4404 / 316L); PEEK; FKM
Process connectionthreaded connection G 1/2 DN15 flat seal
Displays / operating elements
Display
Display unit6 x LED, green (l/min, m³/h, l, m³, 10³, °C)
Switching status2 x LED, yellow
Measured valuesalphanumeric display, 4-digit
Programmingalphanumeric display, 4-digit
Remarks
Remarks
MW = Measured value
MEW = Final value of the measuring range
Pack quantity1 pcs.
Electrical connection
ConnectionConnector: 1 x M12; Contacts: gold-plated
Diagrams and graphs
Pressure loss
dPPressure loss
Qvolumetric flow quantity